FOR TYPICAL REMOTE CONTROL
DETAILS, SEE DOCUMENT
CIRCUIT DRAWN WITH POWER SUPPLY OFF
2
V
2
1
3
4
U
3
PHASE
SUPPLY
RWS100
1
3
6
5
U
V
TRANSFORMER TAPPING OPTIONS
Tap
E
W
FS1
C1
W
X
Y
Z
C2
W
U
X
Y
Z
Nominal 50/60Hz
TYPE 1
220/230
380/400
400,415/420
440/460
FUSE FS1=250mA ANTI-SURGE
PS1
W
X
Y
Z
120VAC 4
_
0VDC
3
24VDC 6
+
TRANSISTOR SWITCHING FOR
24VDC CONTACTORS (IQ10-35)
RELAYS ONLY FITTED WHEN
120VAC CONTACTOR IS FITTED
FOR IQ40,70,90,91 & 95
SK2
0VAC 1
4
24VDC
NOMINAL SUPPLY
(OUTPUT)
5
FUSE FS1=250mA ANTI-SURGE
SK14
0VDC 1
24VDC
X
Y
2
REFER TO SHEET 2 FOR NOTES
& OPTION PCB'S IF FITTED
26 WAY
SK13
6
TORQUE
SENSOR
POSITION
SENSOR
MONITOR RELAY
3
4
3
2
1
2
10 WAY
FS2 (IF FITTED) 100mA
MAKE AT FULLY SHUT
MAKE AT FULLY OPEN
SK9 BREAK AT FULLY SHUT
4
-
BATTERY
1
+
SK14
1
5
SK8
BREAK AT FULLY OPEN
S1
S2
S3
S4
18 WAY
CLOSED
OPEN
REMOTE
STOP
42
43
44
6
7
8
2
8
9
7
3
10
11
6
4
12
13
5
33
34
10
STOP/ MAINTAIN
SK6
SK7
1
SK4
9
CLOSE
50%
TYPE 3
660/660-690
690/-
FUSE FS1=150mA ANTI-SURGE
SK13
SK3
TYPE 2
346/380
480/500
240/240
550/575
OPEN
8
COMMON -VE
1
ESD
12
OPEN INTERLOCK
13
CLOSE INTERLOCK
14
COMMON -VE
5
35
36
25
37
LOCAL
SK1
SLOT A
Iss Date Chkd
Revision Details
5 090113 PMJ Re-track of the 24V DC pin
of SK14 to behind the diode.
6 060614 PMJ 400v added to type 1
tapping Y. Note added to
sheet 2 note 1.
www.
38
31
SK2
SLOT B
.com
IQ BASIC DIAGRAM
ROTORK CONTROLS LTD ROTORK CONTROLS INC Drawn by: PMJ
Date
: 160512
BATH, BA1 3JQ
ROCHESTER
Base WD: 100B0000
ENGLAND
NY 14624, USA
Tel:01225-733200
Tel:585-247-2304
Job No : - MI No : - -
Circuit Diagram Number
100B0000
B1 C1 B2 C2
Issue
No
6
Sheet
1
of 2
IQ3
CIRCUIT DRAWN WITH POWER SUPPLY OFF
NO
OPTIONS
FITTED
NOTES
1.FUSES:
-PS1 is a self-resetting fuse.
-Refer to publication PUB002-039 for approved fuses FS1 and FS2.
-Actuator rated voltage specified on nameplate. Voltage tolerance +/-10%,
applies for rated torque performance; duty cycle is not gauaranteed.
2.REMOTE CONTROL:
-For typical remote control circuits refer to:
-RWS indicated or PUB002-041.
-For DC and AC control, connect –ve/0V to terminal 36.
-(For negative switch / positive common, refer to RWS indicated).
-Control signal threshold voltages:
-DC: “on” ≥16Vdc / “off” ≤8Vdc, max 60Vdc.
-AC: “on” ≥60Vac / “off” ≤40Vac, max 120Vac.
-Control signal duration to be 300ms minimum.
-Maximum current drawn from remote control signals is:
-8mA at 24Vdc or 12mA at 120Vac.
-Supply provided on terminals 4 & 5:
-Intended for remote control.
-Max external load 5W at 24Vdc / 5VA at 120Vac
3.INDICATION:
-For typical position, status and alarm indication see PUB002-041.
-“S” contacts are user configurable and are shown in their default
setting.
-Refer to PUB002-040 for functions and configuration instructions.
-Monitor Relay indicates actuator availability for remote control (shown
“unavailable”). It can be configured to exclude local/remote selection.
-Refer to PUB002-040 for monitored functions and configuration
instructions.
-Voltage applied to indication contacts must not exceed 150Vac
-Individual Switch current must not exceed 3.5A inductive, 5A resistive
and no more than 8A in total for all 4 contacts.
4.BATTERY:
-Battery maintains local and remote “S” contact indication only.
-Refer to installation manual for approved replacement battery types.
See Sheet 1 for all Revision details/information
Circuit Diagram Number
Issue
No
100B0000 6
Sheet
2
of 2
IQ3
Download